New TTE three-phase oil-filled power transformer rated 69/92/115 MVA at 138/34.5/13.8 kV. 60 Hz unit with ONAN / ONAF1 / ONAF2 cooling, vector group YNyn0+d, and tertiary winding for stabilizing purposes only.
Available for sale is one TTE three-phase oil-filled power transformer rated 69/92/115 MVA with voltage ratings of 138 kV / 34.5 kV / 13.8 kV at 60 Hz. The uploaded documentation identifies this unit as new and describes it as unused and stored by the manufacturer. The nameplate drawing shows ONAN / ONAF1 / ONAF2 cooling, vector group YNyn0+d, IEEE C57 standard, and mineral oil insulation fluid.
This transformer is suited to utility-scale, industrial, and power distribution applications where immediate availability may be valuable compared with new production lead times. The technical file references factory testing including insulating level, performance, thermal, auxiliary/mechanical, insulation/material, and CT tests. The nameplate drawing also notes that the tertiary winding is for stabilizing purposes only.
Manufacturer: TTE Transformers
Type: Three-phase oil-filled power transformer
Rating: 69 / 92 / 115 MVA
Voltage: 138 kV / 34.5 kV / 13.8 kV
Frequency: 60 Hz
Cooling: ONAN / ONAF1 / ONAF2
Vector Group: YNyn0+d
Insulating Liquid: Mineral oil
Standard: IEEE C57
Condition: New
Quantity: 1 unit
Year of construction: 2024
Country reference in file: USA
Tertiary winding note: for stabilizing purposes only
Electrical
Rated Power: 69 / 92 / 115 MVA
Tertiary Power Rating: 23 / 30 / 38 MVA
HV Voltage: 138000 GrdY / 79675 V
LV Voltage: 34500 GrdY / 19920 V
Frequency: 60 Hz
Vector Group: YNyn0+d
Standard: IEEE C57
Load Tap Changer: VACUTAP MR 72.5 kV – 18 35 3W
Application: Industrial and power distribution
Tertiary note: Tertiary for stabilizing purposes only
Cooling / Fluid
Cooling Class: ONAN / ONAF1 / ONAF2
Insulating Liquid: Mineral Oil (ASTM D-3487 Type II)
Pressure Rating: Full vacuum
Temperature Rise (Winding / Oil): 65 / 65 °C
Insulation / BIL
Basic Lightning Impulse Insulation Level, Full Wave:
HV: 650 kV
HV Neutral: 200 kV
LV: 200 kV
Losses / Impedance
Short-circuit impedance at 138000–34500 V and 69 MVA: shown on nameplate as field to be completed after final test; value not visible in uploaded files
Weights / Shipping
Total Assembled Weight: 277,340 lb
Tank and Fittings: 55,930 lb
Core and Coils (Untanking): 147,490 lb
Insulating Liquid (Oil): 73,920 lb
Shipping Weight (Without Oil): 187,725 lb
Oil in Each Radiator (50 gal): 360 lb
Total Transformer Weight (including oil) in technical file: 127,797 kg
Shipping Weight in technical file: 85,151 kg
Dimensions (L x W x H): 8.469 x 4.845 x 6.819 m
Included items / accessories noted in the technical file
Winding hot spot temperature detector (RTD)
Winding hot spot temperature indicator relay
Complete set of gaskets
One gallon of touch-up paint
One high-voltage line bushing
One low-voltage line bushing
One neutral bushing (each type)
One sudden pressure relay
One lot breather desiccant
Field services referenced
Offload
Assembly and oil filling
Field inspections and testing
Packaging / shipping
Shipping weight listed
Crate number: Not shown in uploaded files
Package dimensions: Not separately shown
Gross / net packaged weights: Not separately shown
Technical file states unit is stored by the manufacturer and available from February 2026
Offered subject to prior sale and final confirmation of availability. Technical details above are based only on the uploaded documentation and nameplate files. Please contact CTG Power Systems for pricing, delivery terms, documentation review, and project suitability.
Depictions shown herein are representative only and may not reflect the exact final product. Actual equipment will conform to approved engineering documentation and project specifications.
CTG_TTE_STUT-06-3005_Sales_Spec_Sheet.pdf