80/106.4/132.8 MVA ONAN/ONAF/ONAF GSU, 72 kV GrdY to 13.8 kV delta, YNd1, 21-position HV LTC, copper windings. Built December 2015, never placed in service. Stored in Alberta, Canada.
New surplus Hyundai Heavy Industries generator step-up transformer, 80/106.4/132.8 MVA ONAN/ONAF/ONAF, 72 kV grounded-wye to 13.8 kV delta, YNd1, with a 21-position HV on-load tap changer. Manufactured December 2015 to CSA/IEEE standards. Never placed in service. Stored in Alberta, Canada, and available for inspection by appointment.
The unit was oil-filled and nitrogen-blanketed under a December 2024 preservation program, with independent diagnostic testing at that time. Copper windings, full-vacuum tank, conservator and radiators, and a complete set of loose accessories stored in crates.
| Item No. | STT-06-0034 |
| Manufacturer | Hyundai Heavy Industries Co., Ltd., Ulsan, Republic of Korea |
| Type | Generator step-up, two-winding, three-phase, oil-immersed, outdoor, conservator type |
| Manufactured | December 2015 (nameplate) |
| Rating | 80 MVA ONAN / 106.4 MVA ONAF (1st stage) / 132.8 MVA ONAF (2nd stage) |
| Temperature rise | 65 °C top oil / 65 °C average winding |
| High voltage | 72,000 V grounded-wye, neutral brought out (H0) |
| Low voltage | 13,800 V delta |
| Vector group | YNd1 |
| Phases / frequency | 3 / 60 Hz |
| Tap changer | HV on-load (LTC), 21 positions, 79,200 V to 64,800 V (72,000 V ±10%, 720 V steps); change-over selector at mid-range |
| Rated current, HV (tap 11) | 642 A / 853 A / 1,065 A at 80 / 106.4 / 132.8 MVA |
| Rated current, LV | 3,347 A / 4,451 A / 5,556 A at 80 / 106.4 / 132.8 MVA |
| Standards | CSA / IEEE |
| BIL | HV 350 kV / HV neutral 110 kV / LV 110 kV |
| Positive-sequence Z, HV-LV, 85 °C, 132.8 MVA base | Tap 1: 14.731% / Tap 11: 13.947% / Tap 21: 13.384% |
| Zero-sequence Z, HV-LV, 85 °C, 132.8 MVA base | Tap 1: 14.324% / Tap 11: 13.540% / Tap 21: 13.006% |
| Operating altitude | Up to 3,300 ft |
| Sound level | 71.3 dBA at maximum MVA |
| Cooling | ONAN / ONAF / ONAF |
| Winding material | Copper |
| Insulating fluid | Mineral oil, ASTM D3487 Type II (inhibited); 38,403 L (about 10,145 US gal) incl. radiators; PCB-free at manufacture (< 1 ppm) |
| Tank design | Tank, conservator and radiators designed for full vacuum; max. operating pressure at tank cover 10 psi |
| Total, fully assembled | 276,500 lb (125,418 kg) |
| Shipping (without oil) | 182,500 lb (82,781 kg) |
| Untanking | 147,255 lb (66,794 kg) |
| Oil | 76,192 lb (34,560 kg) |
| Dimensions | Per manufacturer's outline drawing, provided in the data package |
| CT | Location | Ratio | Accuracy |
|---|---|---|---|
| 1-3 | HV bushings (1 per phase) | 200/300/800/1200:5 | 0.3B-1.8 at 1200:5 |
| 4-9 | HV bushings (2 per phase) | 200/300/800/1200:5 | C800 at 1200:5 * |
| 10 | HV neutral bushing | 200/300/800/1200:5 | C400 at 1200:5 |
| 11-16 | LV bushings (2 per phase) | 2000/4400/5000/6000:5 | C400 at 6000:5 |
| 17 | Auxiliary | 1420:2 | 1.2CL |
| 18-19 | Auxiliary | 6700:2 | 1.2CL |
* CT 4-9 accuracy class to be confirmed against the nameplate drawing.
Main tank with core and coil assembly and on-load tap changer, plus these components stored loose and crated (final itemized list attached to the quotation):
Not included unless quoted: oil for shipment, foundations, interconnecting bus/cable, protection and control panels.
The outline drawing, nameplate drawing, 2024 preservation and test report, and itemized scope are available to qualified buyers under NDA. To request the data package, an inspection, or a formal quotation, email Sales@CTGPowerSystems.com or call (813) 920-3500 and reference Item STT-06-0034.
Sales / Spec Sheet (PDF): Download Offering Rev. 1 (CTG-OFR-2026-WEB-STT-06-0034-02)
Specifications are from the manufacturer's nameplate and storage and test records supplied to CTG. They are believed accurate but not warranted, and are superseded by the manufacturer's drawings and the formal quotation. Weights are approximate and must be verified before transport planning. This listing is an invitation to inquire, not an offer.